Abstract

Abstract This paper presents a control of distributed generation (DG) system subjected to sudden rise in demand, faults on the distribution feeder and unbalanced load condition. The effects of line to ground faults on the system are investigated and control measures are taken to stabilize the generator speed and to improve voltage quality at the point of common coupling (PCC). The static shunt compensator (STATCOM) is connected at PCC to provide voltage support during sudden demand rise and fault on feeder. Moreover, the STATCOM control is devised such that even during unbalanced load condition the converter current and hydro-turbine–driven induction generator current is balanced. Owing to this, the double power frequency oscillations in the dc-link voltage and torque pulsations in generator can be averted. The STATCOM also supplies reactive power to the load. In addition to this, generation-demand mismatch is moderated using real and reactive power controllers. To demonstrate the performance of the DG system with the said control approach, model of system is simulated in Matlab–Simulink environment and the results are presented.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.