Abstract
This paper focuses on power system stability issues arising under adverse network conditions requiring support from wind farm (WF) electronic converters. The specific instability mechanism investigated refers to a WF participating in emergency reactive support to enhance long-term voltage stability of a weak transmission network. During this support the WF converter may be operating under maximum current limit, in which case it is shown that the WF can become unstable. An aggregate WF equivalent model for voltage stability studies is derived, so as to simplify power system modeling. Protection schemes are proposed to avoid the above-mentioned instability, taking into account the WF converter and pitch control operation. Finally, a typical feeder connecting a WF taken from the Hellenic Interconnected System is simulated as an illustrative case study and the efficiency of the protection schemes proposed is determined.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.