Abstract

This paper presents stability analysis of a distributed generation (DG) controller [1], in an islanded mode, based on the Mapping Theorem and the Zero Exclusion Condition, and validates the results based on a laboratory scale experimental setup. The DG unit is interfaced to the host system through a voltage-sourced converter (VSC). The control strategy regulates the load voltage at the desired value in the islanded mode, despite uncertainties in the load parameters. The frequency of the island is controlled in an open loop manner by an internal oscillator. The experimental results show that the controller provides robust voltage control for a wide range of load parameters, and even maintains the voltage within the prescribed range during the start-up transients of a motor which is part of the island load.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.