Abstract

In the present work, the spray absorption method is studied for the absorption of ammonia refrigerant vapour by lithium nitrate–ammonia solutions. Mass transfer coefficients attainable using the spray absorption method are estimated. In this study the low-pressure absorber of a double-stage absorption refrigeration system is considered. Results show that the mass transferred is maximum (about 60% of the total) during the deceleration period of the drops. This period represents about 13.4% of the time required to reach the equilibrium state at the end of the absorption chamber. The results show that a time-average mass transfer coefficient equal to k m=18.6×10 −5 m s −1 may be attained.