Abstract

The paper present modes of operation of 10(6) kV distribution networks, which are determined by the loads of consumers. The network scheme is based on an open circuit, which allows you to perform calculations for each 10(6) kV distribution line (feeder) separately. The calculation of power losses in the electric network is carried out by the method of average loads. The paper determines the integral characteristics of the operational parameters of the head branch, determines the parameters of the equivalent power loss of the feeder equivalent circuit, and the equivalent circuit determines the energy loss in the feeder. The paper compiles the equivalent circuit of the considered network section, calculated the parameters of the equivalent circuit elements and determines the total power loss in all linear sections. The paper presents an algorithm for calculating the steady state using the example of a feeder and shows the sequence of calculation of current distribution in the branches of the equivalent circuit.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.