Abstract
The article focuses on the residual voltage characteristics of surge protective device during natural lightning induction based on the field observation and lab tests. In natural lighting, induced voltage waveforms and amplitudes generated on the live conductor and the neutral conductor are basically consistent, the amplitude and steepness of the voltage at the household side are higher than those at the AWS collector site, but the continuation time is the same, also are the reverse waveforms and amplitudes. The analysis indicated that the 52m long buried cable reduced the induced voltage gradient and amplitude. Based on the field observation data we utilized impulse current generator to simulate different lightning current waveforms under 1μs steep waveform, 4 /10μs waveform, 8/20μs waveform and 20/60μs waveform, respectively, SPD residual voltage characteristics is discussed in the paper.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.