Abstract
This paper addresses the challenge of fault location in large power networks using a limited number of sensors. It was recently shown that power system faults may be modeled by sparse vectors, and hence, can be located efficiently using sparse recovery techniques. In this paper, we extend this approach and propose a sparse recovery algorithm that exploits both the sparsity constraints and additional structural constraints imposed by the faults physical models. To this end, faults are represented by sparse vectors that are subjected to nonconvex constraints. These constraints are shown to provide additional information that is exploited to reduce the number of measurements and to improve the location accuracy. The algorithm searches directly over these physical faults, and therefore, operates over a small solution space. Simulations on the IEEE 118 bus test-case network show that 4 to 20 sensors are sufficient to recover faults with adequate accuracy. With 20 PMU sensors, more than 99% of single-fault events and 84%-95% of two-fault events are located, depending on fault types and SNR.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.