Abstract

Fault response of an inverter based resource (IBR) is dictated by its control scheme, making it markedly different from the response of a synchronous source. This has led to misoperation of distance relays when fed by IBRs. Published literature is mostly focused on changing the control design of inverters, but this approach is not practical, as these controls are proprietary and beyond the reach of utilities. To resolve this issue, this paper proposes a method for a source-agnostic distance relay that works in time-domain. Using only single ended measurements, the relay detects, classifies and locates any fault on the line it monitors. The method does not require any polarization technique. It is shown to work for unbalanced lines of any length, for transmission or distribution system with any number (even 100%) of IBRs, is immune to load encroachment, decaying dc offset and prefault currents. With very limited communication, it is also shown to be immune to fault resistance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.