Abstract

The sound field in front of, and close to a building facade is relevant to the measurement and prediction of environmental noise and sound insulation. For simplicity it is often assumed that the facade can be treated as a semi-infinite reflector, however in the low-frequency range (50–200 Hz) this is no longer appropriate as the wavelengths are similar or larger than the facade dimensions. Scale model measurements and predictions using integral equation methods have been used to investigate the effect of diffraction on the sound field in front of finite size reflectors. For the situation that is commonly encountered in front of building facades, the results indicate that diffraction effects are only likely to be significant in the low-frequency range (50–200 Hz) when the façade dimensions are less than 5 m. This assumes that there is a point source close to the ground and microphones at a height of 1.2 or 1.5 m, at a distance between 1 and 2 m in front of the façade.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.