Abstract
It is suggested to replace the double-winding transformer of the excitation system of a synchronous machine with a valve-side winding rated for the total forcing voltage and rated current by a three-winding transformer with two valve-side windings, i.e., working and forcing. In the proposed transformer, each of the windings is connected to its own converter bridge circuit and the voltages are summed up during field forcing, which allows the power of the rectifying transformer to be decreased, the shapes of the current and voltage curves at the converter inlet and outlet to be improved, transformer losses and voltage crests on the rotor, and inverse voltages on the thyristors to be reduced, etc.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.