Some experiences on the practical procedure of a boiler ACC are reported.The boiler used consist of a chain grate stoker, a sectional-type water tube, and a single drum, and was heated with coke oven gas and coal, and furnished with Askania regulators with total fuel analog system.We analyzed the control system and actually measured the time constants and examined the setting principle of the master controller and the stability of the control system.From the practical point of view, the theoretical result showed a good agreement with the practical one, which helped us to improve the stability of the system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.