To prevent voltage decrease of distribution systems, the principle and fundamental characteristics of a solid-state current limiter using GTO thyristors were investigated. Basic components of the apparatus were a fast solid-state switch and a current limiting impedance of low resistance in parallel with the switch. Experimental results of the test current limiter showed the fault current was limited successfully, regardless of DC component size. The time from detection of fault occurrence to interruption of the fault current by the solid-state switch was 40 mu s. This time was very short in comparison with that before the fault current reached a large value. Thermal rise of the solid-state switch for conduction was solved by a self-cooling apparatus using a noncombustible cooling liquid. The results indicated that the solid-state current limiter was a valuable protecting device for high fault current distribution systems. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.