Abstract

This paper studies the effectiveness of a solar chimney for improving ventilation and air-exchange rates in multi-storey public housing in tropical climates for the potential mitigation of airborne disease transmission. Virtual models of a typical apartment room with natural cross-ventilation, replicated across four levels to mimic a multi-storey block, were set up with six internal wind velocity sensor points per floor. The simulation software Energy2D was then used to evaluate the performance of the models, first testing the presence of a solar chimney, and then additionally the degree to which the solar chimney model was affected by a complementary ceiling fan. Wind velocity was also measured, as this is a variable that affects ACH rates. Using a non-parametric Wilcoxon signed-rank test, the introduction of a solar chimney was found to have a significant impact on air-flow rates (a variable that positively affects air-exchange rates), resulting in a p-value of 0.000 and Z-value of −3.920. Regression analysis determined that the solar chimney’s effect was enhanced when complemented by a ceiling fan (R-squared value of 0.4687). Consequently, we propose several design strategies that may enable the adoption of the solar chimney concept to improve natural ventilation in residential units.