Abstract

Soil ionisation has an important influence on impulse characteristics of grounding conductor. This paper introduced improvements to an existing soil ionisation model considering the influence of electric field on the change of soil resistivity, while soil resistivity is not directly dependent on soil electric field. The validity of improved soil ionisation model was verified by surge response of vertical conductor in uniform soil and horizontally stratified soil. Furthermore, the impulse experiment was carried out on horizontal conductor in soil with finite volumes. Based on experimental configuration, the corresponding calculation model was built, and calculated results were in good agreement with experimental results.