Abstract
Cooling system is the second most energy-consuming part of a modern data center; herewith it often consumes energy inefficiently. Therefore, any possibility allowing to reduce energy consumption of cooling systems should be studied and put into practice if successful. In this paper, the idea about impact of IT load distribution between servers on energy consumption of data center cooling system is proposed. The idea is in distribution of total IT load between servers according to the location of the servers inside racks. To test idea, the model simulating the thermal behaviour and energy consumption of a real data center located in Northern Sweden is developed. Comparing the data obtained from the real plant and the data generated at the simulation shows the reliability of the model. Two strategies of IT load distribution between servers are considered, and their impact on energy consumption of cooling system is demonstrated.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.