Abstract
This paper presents a small signal stability analysis to assess the stability issues facing PV (photovoltaic) inverters connected to a weak grid. It is revealed that the cause of the transient instabilities, either high-frequency or low-frequency oscillations, is dominated by the outer control loops and the grid strength. However, most challenging oscillations are low-frequency oscillations induced by coupling interaction between the outer loop controller and PLL (Phase-Locked Loop) when the inverter is connected to a weak grid. Therefore, the paper proposes a low-frequency damping methodology in order to enhance the high system integration, while maintaining the stability of the system. The control method uses a DC link voltage error to modulate the reference reactive current. The proposed control reduces the low-frequency coupling between the DVC (DC link voltage controller), AVC (AC voltage controller) and PLL (Phase-locked loop). According to this study’s results, the performance capability of the grid-connected PV inverter is improved and flexibility in the outer loop controller design is enhanced. The control strategy proposed in this paper is tested using the PLECS simulation software (Plexim GmbH, Zurich Switzerland) and the results are compared with the conventional method.
Highlights
High penetration of PV systems into AC systems reduces the grid strength, i.e., the AC system short circuit ratio (SCR) is reduced
The grid strength is described by the SCR, where a weak grid is defined by the SCR < 3 [2]
It has been found that the Phase-Locked Loop (PLL), outer control loop, and the grid strength are the main cause of low-frequency instability issues [4,14]
Summary
High penetration of PV systems into AC systems reduces the grid strength, i.e., the AC system short circuit ratio (SCR) is reduced. References [1,12,13] proposed a reduced small-signal model to investigate the effects of outer control loops, grid dynamics and PLL on the system stability. It has been found that the PLL, outer control loop (which includes the PCC voltage controller and DC link voltage controller), and the grid strength are the main cause of low-frequency instability issues [4,14]. In reference [5], the author proposed a control method to damp the low-frequency oscillations, where the measured PCC voltage is used to update the d-axis current reference, while in [4], the author uses the measured grid current and PCC terminal voltage to set the DC link voltage reference level. A simple compensation method that aims to damp the low-frequency oscillations induced by the outer control loop, the PLL and the grid dynamics, is proposed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.