Abstract
This paper presents test results of forty-eight horizontally unrestrained two-way spanning reinforced concrete slabs at ambient and elevated temperatures. The tests allowed a direct comparison between the modes of failure observed at ambient and elevated temperatures. Both mild steel and stainless-steel welded smooth wire meshes, with varying bar diameters and spacing, were used as reinforcement. The tests at ambient temperature showed that slabs with low reinforcement ratio failed by fracture of reinforcement at the centre of the slab either across the shorter span for the rectangular slabs or across one of the spans for the square slabs. It was found that increasing the reinforcement ratio led to the compressive failure of concrete at the corners of the slabs. Repeating the tests at elevated temperatures showed that all the slabs failed by fracture of reinforcement, with displacements ranging from span/12 to span/6. The results showed clearly that membrane action occurred at both ambient and elevated temperatures, and provides a wealth of data which can be used to further develop simple design methods or validate existing finite-element models.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.