Abstract
With the integration of large-scale wind farm of direct-driven permanent magnet synchronous generator (PMSG) type into power systems, the impacts on the existing power system have to be evaluated elaborately and systematically. This paper will discuss the impact of grid-connected wind farm of PMSG type on power system small signal stability. First, a simplified practical model of wind farm of PMSG type is derived for analyzing small signal stability in this paper. The rotor-flux-oriented control strategy is applied in the modelling of PMSG. Second, the simulation scenario involving replacing synchronous generator with wind farm of PMSG type based on the IEEE 3-generator-9-bus test system as benchmark is carried out to conduct the eigenvalue analysis and to assess the effect of wind farm of PMSG type on power system small signal stability. Finally, some preliminary conclusions and comments are drawn according to the simulation results.