Abstract
In this paper, an improved analytical small signal model of the line commutated converter (LCC) is developed in direct-quadrature-zero coordinates based on the assumption of infinite six-pulse converters. The dynamics of the commutation inductance and transportation delays during commutation are included in the model, and the sampling of the measurement of firing and extinction angles is added to accommodate actual converters with a finite pulse number (e.g., 12-pulse). The model is validated by comparing the frequency response with one obtained by frequency scanning in an electromagnetic transients (EMT) simulation. The model is shown to be effective in investigating system stability when the LCC is connected to an arbitrary external network. To do this, the frequency response of the combined system is plotted, and the generalized Nyquist stability criterion is applied. This stability result is validated by a time domain simulation on an EMT program using the first CIGRE HVDC benchmark system and the IEEE 14-bus system. Compared to the traditional LCC model, the proposed model is shown to have significantly better accuracy in system stability determination.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.