Abstract

The COVID-19 pandemic has underscored the need for effective ventilation control in public buildings. This study develops and evaluates a smart ventilation control algorithm (SIREN) that dynamically adjusts zone and system-level HVAC operation to maintain an acceptable COVID-19 infection risk and HVAC energy efficiency. SIREN uses real-time building operation data and Trim & Respond control logic to determine zone primary and system outdoor airflow rates. An EnergyPlus and CONTAM co-simulation framework was developed to assess its performance across various control scenarios and US climate zones. Results show that SIREN can flexibly control infection risk within a customized threshold (e.g. 3%) for every zone, while traditional controls cannot. At the building level, SIREN’s HVAC energy consumption is comparable to a fixed 70% outdoor airflow fraction scenario, while its infection risk is lower than the 100% outdoor airflow scenario, illustrating its potential for safe and energy-efficient HVAC operation during pandemics.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call