Abstract
Definite-time zero-sequence over-current protection is presently used in systems whose neutral point is grounded by a low resistance (low-resistance grounding systems). These systems frequently malfunction owing to their high settings of the action value when a high-impedance grounding fault occurs. In this study, the relationship between the zero-sequence currents of each feeder and the neutral branch was analyzed. Then, a grounding protection method was proposed on the basis of the zero-sequence current ratio coefficient. It is defined as the ratio of the zero-sequence current of the feeder to that of the neutral branch. Nonetheless, both zero-sequence voltage and zero-sequence current are affected by the transition resistance, The influence of transition resistance can be eliminated by calculating this coefficient. Therefore, a method based on the zero-sequence current ratio coefficient was proposed considering the significant difference between the faulty feeder and healthy feeder. Furthermore, unbalanced current can be prevented by setting the starting current. PSCAD simulation results reveal that the proposed method shows high reliability and sensitivity when a high-resistance grounding fault occurs.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.