Abstract

The single line-to-ground (SLG) fault is a research focus, considering it is amongst the top frequent occurrences of faults in distribution systems. The neutral point treatment is crucial for continuous safe operation of distribution systems. However, the traditional arc suppression coil cannot compensate for the active component in ground current. Therefore, we present a single-phase flexible arc suppression device (SFASD) based on backstepping control and second-order generalized integrator phase-locked loop (BSC-SOGI-PLL) method. The SFASD with a cascaded H-bridge (CHB) topology is connected to the neutral point of distribution systems for eliminating the ground current. The comparisons between the BSC-SOGI-PLL and the BSC method concerning the effect of arc suppression are discussed. The effectiveness of the proposed SFASD based on the BSC-SOGI-PLL components for arc suppression is verified on the scale-down experimental platform.