Abstract

Liquid desiccant cooling system (LDCS) is a novel air-conditioning system with good energy saving potential. However, the present LDCS has a poor performance, mainly because the conventional thermal regeneration method wastes too much energy during the regeneration process. To improve that, photovoltaic-electrodialysis (PV-ED) regeneration method is introduced: it has a higher performance by using solar photovoltaic panels to drive an electrodialysis regeneration process. To further explore the PV-ED method, both single-stage and double-stage photovoltaic-electrodialysis regeneration systems are presented in this paper. Analysis is made on these two systems and some influential factors are investigated. It reveals that the concentration difference between the desiccant solution before and after regeneration has a strong impact on system performance. Moreover, comparison is conducted between the single-stage and the double-stage systems, the results show that the double-stage system is more energy-efficient and it can save more than 50% energy under optimized working conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.