Abstract

The main purpose of this paper is to provide a methodology to monitor harmonics produced by power transformers during geomagnetic disturbances. The advocated scheme leverages the existing infrastructure and is based on the embedded operating quantities of microprocessor-based differential protection relays. The characteristics of single-phase transformer magnetizing current are discussed. The second harmonic signature is a good indicator of half-cycle saturation and can be mapped into an effective geomagnetically induced current. The proposed scheme was tested in closed-loop using a real-time digital simulator and validated with field measurements.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.