Abstract
Single-phase operation of a three-phase induction generator with the Smith connection (SMIG) is analyzed using the method of symmetrical components. It is shown that, despite the asymmetrical nature of the winding connection, balanced currents can be made to flow in the three-phase stator winding. The conditions for achieving perfect phase balance are carefully deduced. With the aid of a phasor diagram, expressions for the line power factor and line current under perfect phase balance are also obtained. The effect of the phase-balancing capacitances on the generator performance is investigated. A simple dual-mode control scheme is also proposed with a view of minimizing the phase imbalance over the practical operating speed range. Experiments conducted on a 2.2-kW induction machine confirm the validity of the theoretical analysis and feasibility of the control method.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.