Abstract

After a single-phase high-impedance fault (HIF) for low-resistance grounded distribution network (LRGDN) occurs, fault current level is very low and cannot be detected by conventional overcurrent relays. In this study, composite power of each feeder which is composed of complex power and its conjugate is defined, and a HIF protection method based on the composite power of each feeder is presented. For a sound feeder, the phase angle of the composite power is equal to 0, and its amplitude is approximately 0. However, for the faulty feeder, the phase angle of the composite power is π, and its amplitude is much greater than 0. Base on the above significant difference, the protection criterion for HIFs in the LGRDN can be obtained. Theory analysis and simulation results show that the proposed method does not need to check the polarities of the zero-sequence current transformers and is able to remove faulty feeder reliably. Besides, the protection can accurately operate for HIFs in the case of noise interference and unbalanced current. The experimental results based on RTDS also show the efficiency of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.