Abstract
This report presents results from an ASHRAE-sponsored research project designated RP-1067. The objective of this study was to document the heat transfer and pressure drop phenomena of selected refrigerants in a superheated state with lubricant mixtures. Refrigerants used in this study included R-22, R-134a, R-407C, and R-410A. This paper presents the smooth tube results over a Reynolds number range of 100,000 to 1,000,000, with lubricant concentrations ranging from 0% to 5% by mass. The refrigerant saturation temperature was maintained at 40°C, which would be common for the inlet of a condenser. The results show that even small additions of lubricant cause significant increases in pressure drop. The lubricant also causes a less dramatic increase in the heat transfer coefficients. Models are proposed to allow prediction of superheated refrigerant and lubricant mixture performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.