Abstract
Previous work on parameter error identification that is based on calculation of Lagrange multipliers has shown that the errors on single edge cutsets could not be detected and errors on double edge cutsets could not be identified without incorporating phasor measurement units (PMUs). Hence, the first step to address such deficiencies is identification of all single and double edge cutsets for large scale power networks. This paper presents a numerically efficient method which relies on factorization of reduced incidence matrix of the network. Results obtained by implementing the method in IEEE 14-, 30-, and 57-bus test systems and a 4520-bus transmission system are presented to illustrate its computational performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.