Abstract
Detection apparatus which allows the simultaneous recording of TL and TSEE curves up to 650 K after X or UV irradiations at 77 K is described. Various samples of a-alumina were studied in these conditions. It is shown that this approach avoids some measurement errors and compares accurately the TL and TSEE peaks related to the same trapping centre.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.