Abstract

In this paper, it established the single-phase to ground fault model of small current to ground system, and simulated the model, according to decomposed by EMD algorithm for transient zero-mode power signal of every detection point along the line installed. It utilized the high-frequency IMF components got to subtract backward first-order, according to analysis the differential waveforms of every detection point, it has the differential waveforms similarity degree of two detection point located the same side of fault point is higher, while the differential waveforms similarity degree of two detection point located the two sides of fault point is lower. In addition, if the fault point was center, the differential waveform symmetry of two sides of fault point is higher. Besides, it has shown that the characteristic information of first-order differential waveform was not varied by the transition resistance’s change. So it utilized the characteristic information of differential waveform to provide a new idea for fault location of small current to ground system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.