Abstract

The dielectric recovery characteristics are very important for the successful interruption of the vacuum circuit breaker. In order to explore the influence of the post-arc dielectric recovery characteristics of the multi-break vacuum circuit breaker on its breaking, this article establishes a simulation model of the multi-break vacuum circuit breaker and a 750kV short line fault simulation circuit in MATLAB. By adjusting the dielectric recovery characteristics of different breaks, the critical dielectric recovery rate (The minimum dielectric recovery rate of the break when the circuit breaker does not break down) under different conditions is finally obtained. In addition, the influence of the equalizing capacitor on the critical recovery rate is also explored. It is found that the smaller the grading capacitance, the greater the voltage of the break, and the greater the critical dielectric recovery rate.