Abstract

In order to obtain a better understanding of flow characteristics of displacement ventilation, the three-dimensional numerical models are developed using the CFD technology. The numerical simulation results are verified by experiments, based on this, the velocity and temperature distribution of three-dimensional displacement ventilation system with single and double heat sources are studied. Velocity and temperature fields under two different cases of heat source are analyzed and compared. The numerical results show that there are three layers in vertical temperature fields of displacement ventilation system with single or double heat sources, and the vertical temperature distribution of single heat source is different from that of double heat sources. When indoor load is large, the comfort requirement of people indoor can’t be satisfied with displacement ventilation system only, thus an additional refrigeration system is necessary. Furthermore, under the condition of two heat sources, the displacement ventilation parameters can’t be computed simply according to single heat source inlet parameters, therefore the interaction between heat sources should be considered.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.