Abstract

The main steam temperature process has the characteristics of large inertia, large time delay and time-variation , to solve this problem, the fuzzy PID cascade control system with Smith predictor is presented .The improved Smith predictor with the effect of filtering was used in the main loop of the cascade control system, and fuzzy PID compound controller was used as the main controller based on the advantage of fuzzy control and PID. Through establishing the mathematical model and simulating the main steam temperature control system, either the parameter changed or invariable, the results show that the method can improve the control qualities and enhance the robustness and stability of the control system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.