Abstract
A high-altitude electromagnetic pulse (HEMP) may pose a significant threat to the electrical power grid. In this context, the present study considers the potential impact of the HEMP early-time component (E1) on the winding of a typical transmission power line transformer. A time-domain, fully electromagnetic, three-dimensional, finite-element model was used to simulate the propagation of an E1-induced voltage surge into the transformer winding. The analysis is focused on the first few turns of the winding, the ones that are impacted by the largest electric field resulting from the applied pulse. The model follows the transient dynamics, while the pulse is traveling along the conductor, and the electric field is established across the insulation gaps through capacitive coupling. The simulations also considered the effect of an electrically floating, “shield” winding conductor. This is used as a countermeasure to improve the voltage uniformity across the winding during fast-rise transients. In this case, the propagation of the E1-induced pulse is compared with that from a slower rising, lightning standard waveform. The simulation results show that the presence of the shield conductor can effectively reduce the peak electric field between winding turns, in the presence of either E1 or lightning waveforms.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Electromagnetic Compatibility
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.