Abstract

A computerized simulation of a simple single-stage vapour-compression refrigeration system has been made. The steady-state simulation uses the accurate property correlations developed by Cleland for refrigerant R134a. The inputs to the program are: evaporator pressure, condenser pressure, superheating at evaporator outlet, subcooling at condenser outlet and compressor isentropic efficiency. The program outputs are: refrigerating effect, compressor work input, coefficient of performance (COP) and suction vapour flow rate per kW of refrigeration. An increase in the evaporator pressure from 150 to 250 kPa improves the COP by 40%. The COP is decreased by 35% when the condenser pressure is increased from 1000 to 1500 kPa. Increasing the superheat at the evaporator outlet from 0 to 160C improves the COP by 2.6%. An increase in subcooling at the condenser outlet from 0 to 160C increases the COP by 20%. The COP is improved by 150% when the compressor isentropic efficiency is increased from 0.4 to 1.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.