Abstract

Disconnector switching in gas insulated switchgear (GIS) generates very fast transient overvoltage (VFTO). VFTO may damage the insulation of GIS equipment. This paper studies the VFTO of a 1000kV GIS substation. The simulation models are obtained according to the configuration of GIS. Operation modes of disconnector were summarized. The characteristics of VFTO were obtained. During the system commissioning test of the substation, VFTO were measured during disconnector switching. Comparison was made between the test and simulation results. The simulation results were in agreement with the test results. The accuracy of the simulation model is verified. Simulation and test study shows that it is safe to do switching operation of disconnector in this GIS substation without damping resistor.