Abstract
Control strategies for extracting the three-phase reference currents for shunt active power filters are compared, evaluating their performance under different source conditions in MATLAB/Simulink environment and also with Real Time Digital Simulator (RTDS) Hardware. When the supply voltages are balanced and sinusoidal, the two control strategies are converging to the same compensation characteristics but when the supply voltages are distorted and/or un-balanced sinusoidal, these control strategies result in different degrees of compensation in harmonics. The p-q control strategy is unable to yield an adequate solution when source voltages are not ideal. Extensive Simulations are carried out with PI controller for both p-q and Id-Iq control strategies for different voltage conditions and adequate results were presented. The 3-ph 4-wire SHAF system is also implemented on RTDS Hardware to further verify its effectiveness. The detailed simulation and RTDS Hardware results are included.
Highlights
Harmonics surfaced as a buzz word from 1980’s which always threaten the normal operation of power system and user equipment
Sinusoidal voltage is a conceptual quantity produced by an ideal AC generator built with finely distributed stator and field windings that operate in a uniform magnetic field
Since neither the winding distribution nor the magnetic field are uniform in a working AC machine, voltage waveform distortions are created, and the voltage-time relationship deviates from the pure sine function
Summary
Harmonics surfaced as a buzz word from 1980’s which always threaten the normal operation of power system and user equipment. In particular, cause enormous economic loss every year. Owing both power suppliers and power consumers are concerned about the power quality problems and compensation techniques. Sinusoidal voltage is a conceptual quantity produced by an ideal AC generator built with finely distributed stator and field windings that operate in a uniform magnetic field. Since neither the winding distribution nor the magnetic field are uniform in a working AC machine, voltage waveform distortions are created, and the voltage-time relationship deviates from the pure sine function. It is noted that non-sinusoidal current results in many problems for the utility power supply company, such as: low power factor, low energy efficiency, electromagnetic interference (EMI), distortion of line voltage etc. The 3-ph 4-wire SHAF system is implemented on a Real Time Digital Simulator (RTDS Hardware) [5] to further verify its effectiveness
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: Engineering, Technology & Applied Science Research
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.