Abstract

In this paper, we will analyze Partial Discharge (PD) in a typical Gas-insulated substation and the voltage signals are simulated in bus bars and different elements such as transformers in presence of PD and normal state. Then, the corresponding carves compare with together. For this means, we simulate sheikh bahayi substation in Tehran as a 400kv GIS substation in EMTP software. First, very fast transients(VFT) model is used for the GIS substation modeling. Then, voltage signal of different points of GIS substation in presence of PD are measured by use of the PD model in gas insulator and VFT model, until the PD effects on system voltage is determined. Keyword: GIS Substation, Partial Discharge, VFT Method, Digital Simulation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.