Abstract

In thermally modernised buildings, sharing of ventilation heat loss becomes more significant. In the case of the application of ventilation with heat recovery, especially during transitional periods, there arises a question of whether an air system makes it possible to maintain the required indoor air temperature without the necessity of using a basic hydronic heating system. This paper presents the application of a simple thermal network model of a building zone to simulate indoor air temperature in a single room of a multi-storey building with a mechanical ventilation system with heat recovery. Ventilation air was supposed to be the only heat source and its ability to maintain the required indoor air temperature was checked in simulations and then compared with measurements. The 5R1C thermal network model of a building zone was used for simulations. Comparison with measurements showed the Mean Absolute Error (MAE) and Root Mean Square Error (RMSE) of indoor air calculation to be 2.37 °C and 2.45 °C, respectively. When including heat flux from the bottom storey through the floor, MAE = 1.28 °C and RMSE = 1.38 °C were obtained.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.