Abstract

So as to research impact of inlet temperature of gas cooler on the expression of carbon dioxide hot water unit, the ambient temperature was controlled at 15 °C, and the inlet temperature was adjusted. The exhaust temperature, heating capacity, and system heat exchange capability were calculated. Testing and measuring the change of exhaust temperature, outlet temperature of gas cooler, exhaust pressure, heat exchange capability. Based on simulink simulation tools, a calculation simulation platform of CO2 heat pump water heaters was established, and a test bench of transcritical CO2 heat pumps was built. In the experimental simulation, the inlet water temperature was increased from 15 °C to 40 °C, the simulation result of the exhaust temperature increased by 14.2 °C, the heating capacity decreased by 4.69 kW, the heat pump coefficient decreased by 0.66. In the experimental result, the exhaust temperature increased by 18.7 °C, the heating capacity decreased by 4.31 kW, heat pump coefficient decreased by 0.63. The research results can provide some guidances for the practical application and optimization of transcritical CO2 heat pump system.