Operating characteristics of variable cross section area of main duct in the main-branch central exhaust system was simulated based on various stories, operation rate and cross section area of main duct by FLUENT. The results show that there are certain obvious induced flow in the lower part of the system when the users in the upper floor work in the central exhaust system,and the internal pressure of main duct appears low- high-low trend in the system from the bottom to the top floor. The maximum pressure position is not in the bottom, but in the middle and lower floor of the system, where is the most disadvantageous floors of the exhaust system. It indicates that 400 mm x 500 mm is the necessary cross section area of main exhaust duct for 10 layers buildings,and 400 mm x 750 mm is the necessary one for 20 layers buildings.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.