Abstract
When the transformer is switched on without load, the magnetizing inrush current will be caused due to the saturation of the iron core, which may lead to the misoperation of the relay protection device, cause overvoltage and damage the insulation of the equipment. To solve this problem, EMTP/ATP software is used to simulate the no-load closing of three-phase transformer, the applicability and accuracy of BCTRAN model in the simulation of no-load closing of transformer are studied, and the inrush current waveform under different closing angles and residual magnetism is analyzed. The results show that the BCTRAN model can simulate the hysteresis characteristics of the core by adding external nonlinear elements, and the calculation results are more accurate.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.