Abstract

The modular simulation model of MW-level grid-connected photovoltaic (PV) power station is established at PSCAD/EMTDC. In this paper, simulation models according to different real engineering can be set up based on the modular flexible combinations. Next, power quality of PV power station and influence on distribution networks are studied. In addition taking a real system for example, the voltage deviation and the harmonic distortion (THD) of distribution networks connected with the different scale gridconnected photovoltaic power station are analyzed. The conclusion that voltage deviation of distribution networks may exceed limits of national standard with the expansion of PV capacity is drawn. This paper puts forward reactive power control method of the station based on synchronous PI current control .Finally, the harmonic current generated by the 10MW PV power station is analyzed. (6 pages)

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.