Abstract

Steel pole structures are suitable alternate to transmission line towers, due to difficulty encountered in finding land for the new right of way for installation of new lattice towers. The steel poles have tapered cross section and they are generally used for communication, power transmission and lighting purposes. Determination of deflection of steel pole is important to decide its functionality requirement. The excessive deflection of pole may affect the signal attenuation and short circuiting problems in communication/transmission poles. In this paper, a simplified method is proposed to determine both primary and secondary deflection based on dummy unit load/moment method. The predicted deflection from proposed method is validated with full scale experimental investigation conducted on 8 m and 30 m high lighting mast, 132 and 400 kV transmission pole and found to be in close agreement with each other. Determination of natural frequency is an important criterion to examine its dynamic sensitivity. A simplified semi-empirical method using the static deflection from the proposed method is formulated to determine its natural frequency. The natural frequency predicted from proposed method is validated with FE analysis results. Further the predicted results are validated with experimental results available in literature.