Abstract

The article presents the simplified implementation of alternative load path method based on the energy balance approach. This method should be used to check the global resistance of a damaged structural system after the occurrence of an accidental event. Basic assumptions of simplified analytical models for modelling resistance of horizontal ties in a damaged structural system, taking into account the membrane (chain) effects, were presented. An approach to modelling the dynamic resistance of a damaged structural system based on the energy balance method is described. Calculated dependencies for checking the robustness of a prefabricated multi-storey building with hollow-core slabs after the loss of the central column are proposed and considered using an example. On the considered example, a comparison of the required tie sections area with the dynamic resistance designed using the energy balance method (EBM) and according to the current standards, and a statistical assessment of the reliability of the load-bearing capacity models are carried out. In the end, a brief algorithm for the simplified calculation of the dynamic resistance of a damaged structural system is proposed.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.