Abstract

A new simple estimation model was described on excess temperature and velocity of ceiling jet under the flat, horizontal and sloped ceiling of an unconfined room from a t²-fire. This simple model was composed of ceiling height (H), distance along ceiling from the impinging point (r), and heat release rate (Q) which was given as a t²-fire. This model was verified by the experimental data which were conducted using at² model fire with ceiling heights of 2m, 2.1m, 4m, 8m, 15m and 20m. Flat and sloped ceiling with smooth surface was also used as a model ceiling, and those experimental data were used to verify the model. This model can deal with the cases of a corner fire and a wall fire for its early stages, and also verified by the data of corner and wall fires. The model for excess temperature and velocity with suitable RTI gave the estimation on the operation time of heat detector and sprinkler.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.