Abstract

The negative impacts or side effects of a damper circuit insertion in an LCL passive filter utilized to filter DC/AC inverters output voltage is presented in this paper. For comparative study, this paper discusses two damping configurations, namely series and parallel damping, as well as the LCL filter without damping element. Four criteria are used to explore the impacts of the damper circuits, i.e. their total harmonic distortions (THDs), the output voltage amplitude, the output power and the power efficiency. Theoretically and emphirically shown by previous studies, the damper can indeed reduce the peak resonance frequency of the filter in its frequency response curve. However, in any circumstance, it can potentially reduce the inverters power and efficiency, voltage output amplitude, and cannot improve its THD reduction. The analysis results have shown that the side effects depends also on the load conditions, which are different for each damping circuit configuration.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.