Abstract

Fault level considerations may be an inhibiting factor for the interconnection of distributed generation (DG) to the network, particularly at the medium voltage level. In this paper, the latest edition of the IEC 60909 Standard is applied for the calculation of the resulting fault level in medium and low voltage distribution networks with DG. First, an outline of the IEC calculation methodology is presented, including all relevant equations for DG cases studies. Then the short-circuit contribution of the various DG types is extensively discussed. The application of the methodology is demonstrated on a study case medium voltage distribution network, which includes all representative types of DG sources. Emphasis is placed on the contribution of the upstream system, which is the dominant source of short-circuit current. A discussion is also included on potential measures for fault level reduction.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.