Abstract
Convective vaporization data were obtained on a staggered tube bank made of 18.9 mm (0.75 inch) outside diameter integral fin tubes (1024 fins/m; 26 fins/inch) with an equilateral pitch-to-diameter ratio of 1.25. Data are presented for pure Refrigerant-11 with saturation temperatures of 4.4°C (40°F) and 26.7°C (80°F). The data span vapor qualities of 0 to 0.9, mass velocities (based on minimum flow cross section area) of 7 to 18 kg/m2·s (5,200 to 13,300 lb/h·ft2), and heat fluxes of 15 to 45 kW/m2 (4,800 to 14,300 Btu/h·ft2). The data were taken in an apparatus that allows independent control of vapor quality, mass velocity, and heat flux. In contrast to the data presented on enhanced tubes in Part 2, the convective effects strongly influence the integral finned tube performance. The Chen superposition model (with or without using a suppression factor) largely under-predicted the data. The data were correlated in the form of an asymptotic model. The correlations fit 92% of the data within ±20%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: HVAC&R Research
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.