Abstract

AbstractThis paper presents shake table test results on two identical 1:0.429 scaled, 8-story moderately ductile RC shear wall specimens under the expected high-frequency ground motion in eastern North America. The walls were designed and detailed according to the seismic provisions of the NBCC 2005 and CSA-A23.3-04 standards. The objectives were to validate and understand the inelastic responses and interaction of shear and flexure and axial loads in the plastic hinge zones of the walls taking into consideration the higher-mode effects. One specimen was tested under incremental ground motion intensities ranging from 40 to 120% of the design level. The intensity range was increased from 100 to 200% for the second specimen. The response of the walls was significantly affected by the second mode, causing an inelastic flexural response to develop at the base as well as at the sixth level. Dynamic amplification of the base shear forces was also observed in both walls. In the second wall, which was tested in t...